Sequence of Operation
System Sequence of Events
Objective Equipment List
¨ Apex Destiny 6100 control panel,
rev. 8.05 or greater
- Delayed Extended Monitor -
Provide extended monitor for a
zone if it remains open after a
specified time delay period.
When Zone 1 opens and remains open for a specified time delay period, the system will annunciate
the zone opening for the programmed extended monitoring time (default is 30 seconds). If Zone 1
opens and then closes before the specified time delay period has expired, there will be no extended
monitoring.
1) Zone 1 opens sending an ON command to Control Channel 1.
2) Control Channel 1 (Chain Channel 1) first energizes the on-board relay (Auxiliary Output 8) and then
Auxiliary Output 1. The ground signal from Auxiliary Output 1 is now available at the normally closed
(NC) terminal of the on-board relay.
3) The on-board relay will return to its normally closed position after the automatic turn-off time period
and allow the ground signal from Auxiliary Output 1 to activate Zone 3. Zone 3 is programmed as a
Day zone that will always be an extended monitoring zone when the system is disarmed.
4) If Zone 1 opens and then closes before the automatic turn-off time period has expired, Zone 2 closes
sending an OFF command to Control Channel 2 (Chain Channel 2) which first deenergzes Auxiliary
Output 1 and then the on-board relay. This will prevent the Auxiliary Output 1 ground signal from
activating Zone 3.
This application may be used in a residential or light commercial installation to give an
audible notification when a zone (door, window, cabinet, pool gate, display case) is
opened and not properly closed or left open.
Apex Technical Support 800-272-7937
Option 1
Page 5-3